VentiSketch is a concept-stage design tool, so we say plainly how accurate it is, and where you should allow a margin.

What we checked

Before the first release we compared VentiSketch with published wind-tunnel data, full-scale measurements and standard formulas from the ventilation literature.

29wind-tunnel cases checked for the 2D model and ACH
±11%mean difference in flow through the building, per test set
≤2%buoyancy in section against the standard formula
0.923D wind tunnel windward–leeward pressure difference (usual design value ~0.9)
  • 2D model and ACH: isolated buildings at several wind angles, building arrays and many opening layouts
  • 3D wind tunnel: wind pressure on a standard 6 m cube; windward and roof values fall within the measured range, and results barely change on a finer grid

Limits you should know

  • Large openings: with openings over 15% of the wall the flow is underestimated, and the report warns you
  • Side walls in the 3D wind tunnel: suction may be about 15–30% low, so ACH for air leaving through side walls may be slightly low (on the safe side)
  • Level of result: plan and section results are concept-level estimates for comparing design options, not research-grade CFD or structural wind loading
  • Resolution: use at least Medium for numbers; Low is for seeing the flow pattern
Results are not a substitute for engineering analysis, full 3D CFD, on-site measurement or statutory checks (see clause 8 of the licence agreement).

Institutions that need the details of the test method can contact support@ventisketch.com